Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 13 Next »

Hydropower is modelled as a combination of a downstream hydropower demand, a hydropower release, and the energy that is subsequently generated by this release.

  • The hydropower demand is represented in the model as a water demand at the turbine(s).
  • The hydropower release is the release from storage required to meet the hydropower demand; this may be a combination of the release made to meet other downstream demands and an additional release made to meet the full hydropower demands.
  • Hydropower generation is the energy generated and is a function of the discharge through the turbine, head, turbine efficiency and time.

Turbines are assumed to be attached to storage outlet valves (as shown schematically in Figure 31) and there may be more than one turbine associated with each outlet. It is possible to configure storages with multiple outlets that could include multiple valve outlets with turbines.

Figure 31. Estimation of total head to turbine outlet

Scale

This node represents a location and can therefore be considered to be site scale. It is used at every model time step.

 

Principal developer

eWater CRC

 

Version

Source v3.8.8

 

Dependencies

Hydropower is one of the features associated with the storage node.

 

Availability/conditions

Automatically included with the product.

 

Flow phase

Calculation of hydro-electric energy generated

The energy generated is a function of the discharge through the turbine, total head (see Figure 31) and turbine efficiency over the time step. The turbine efficiency is assumed to be constant for a given discharge and head, which is a simplification. The calculation of energy generated, in megawatt hours (MWh), during each model time step is:


Equation 130

Where

P the energy generated (MWh)

e the turbine efficiency (%)

h the average total head to the turbine outlet during the model time step (m)

Q the average discharge through the turbine during the model time step (m3/s)

t is model time step (h)

If the energy generation calculated via Equation 131 exceeds the hydropower demand then the energy result is set to be equal to the demand.

The total head, h, is evaluated by Equation 131, where the terms are defined as shown in Figure 31:


Equation 131

Where

hx1 the head above the valve inlet at the beginning of the time step (m)

hx2 the head above the valve inlet at the end of the model time step (m)

ht the head difference from the valve inlet to the turbine outlet (m)

It should be noted that this formula is a simplification as the energy should be estimated by integrating Q and h across the time step. Given that the change in head and discharge during the time step can be expected to be small this is a reasonable approximation.

 

Calculation of discharge through turbines

The storage node calculates storage release in response to storage demand, subject to outlet constraints such as the maximum release for each valve. The storage release represents the water that is controlled release as well as water that spills, and may occur through a combination of culverts, pumps, valves, gated spillways and ungated spillways. The storage demand represents the total of all downstream demands. The maximum release curve for each valve is entered in the form of a storage-discharge relationship and comprises part of the total minimum and maximum release curves.

The discharge through the turbines in each model time step is calculated as the minimum of the storage demand and the total of the turbine release curves (ie valves with turbines), for the given head, during the time step.

 

Prioritisation/scheduling of turbines

The assumption is that any storage release to meet downstream demands of whatever type will occur through the turbines first, on the basis that hydropower would be generated to meet hydropower demands whenever possible. If the hydropower demand exceeds the sum of turbine outlet capacities then all turbines are assumed to be operating. However, if the hydropower demand is less than the sum of turbine outlet capacities than a decision needs to be made about what turbines are operating. The assumption is that highest generation potential gets priority. Priority is evaluated considering head and efficiency as in Equation 132, below. The highest value will get the highest priority and so on until the demand is satisfied.

Equation 132

Prioritisation is illustrated in the Two Turbine Example below.

 

Single Turbine Example

A storage has one valve, which is connected to a turbine. The turbine has a head difference (ht) of 100 m and an efficiency of 80%. The storage has a head (hw) of 260 m above dead storage and the valve invert (hv) is 10m above dead storage. Based on the definitions in Figure 31:

Equation 133

The head drawdown is assumed to be negligible during the model time step which is one day. Therefore, from Equation 131:

 

Equation 134

At 350 m head the turbine can potentially let out 100 m3/s but the total demand in the current time step is only 50 m3/s; hence the required discharge through the turbine is 50 m3/s and from Equation 130 the energy generated is:

Equation 135

Two Turbine Example

A storage has a head (hw) of 260m above dead storage. The storage has two valves, both connected to turbines. The head drawdown is assumed to be negligible during the model time step which is one day.

Turbine1 has a head difference (ht1) of 100 m and an efficiency1 of 80%. The valve invert (hv1) is 10 m above dead storage. Based on the definitions in Figure 31:


Equation 136

Turbine2 has a head difference (ht2) of 50 m and an efficiency2 of 90%. The valve invert (hv2) is 20 m above dead storage. Based on the definitions in Figure 31:

Equation 137

Therefore, from Equation 131:



Equation 138

 

At 350 m head, turbine1 can let out 100 m3/s while, at 290 m head, turbine2 can let out 50 m3/s; the combined potential discharge is 150 m3/s. However, the total demand in the current time step is only 125 m3/s. Therefore the required discharge through the two turbines is 125 m3/s and utilisation of the two turbines needs to be prioritised.

Turbine priority is calculated using Equation 132 as follows:


Equation 139

 

Priority1 is greater than priority2, therefore turbine1 has priority. Turbine1 is fully utilised first with 100 m3/s, which leaves turbine2 with:

Equation 140

 

From Equation 130 the energy generated is:



Equation 141

Key assumptions and constraints

Assumptions:

  • Turbine efficiency is assumed to be fixed whereas in reality it is a function of head and flow rate.
  • The energy calculation is not integrated across the time step as it is assumed that the change in head will be small. There may be cases where this is not true.

Constraints:

  • Sub-time-step releases and energy calculations are not accommodated. These can be modelled by reducing the model time step or assuming the peak demand is averaged across the time step.
  • No labels